Understanding IAC Operation
4-5
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
4.2.3 Redundant Operation with Maintenance Bypass – Bypass Mode
The wraparound MBP is closed, supplying the critical load with bypass power. The MIS is
opened, isolating the UPMs from the load. The MOBs may be opened to isolate the
individual UPMs.
The critical load is not protected while the system is in Maintenance Bypass mode.
Figure 4-5 shows the path of electrical power through the IAC during redundant operation
when bypass is in maintenance mode.
OUTPUT TO
CRITICAL LOAD
IAC
MIS
MBP
MAIN POWER FLOW IN UPS MODE
MAIN POWER FLOW IN MAINTENANCE BYPASS MODE
MOB 1
MOB 2
FROM UPM 1
OUTPUT
FROM UPM 2
OUTPUT
AC INPUT TO
BYPASS FROM
UTILITY
Figure 4-5. Path of Current Through the IAC during Redundant Operation in Bypass Mode
Summary of Contents for Powerware 9390 IAC-B
Page 145: ......
Page 146: ...164201590C 164201590 C...