71
Mounting- and Operating Instruction Eaton LoadStar-S JSB
40071860396 March 2021 www.ceag.de
33 3-PM-IO Module
33 3-PM-IO Module
In order to avoid the risk of power failures, it is necessary
to permanently monitor the function of the general lighting
light distributors in order to switch on the safety lighting in
the event of a fault. The 3-PM-IO modules are therefore an
important part of the safety system. The safe functioning
of the entire system must be constantly monitored and, in
the event of faults, the system must switch on the safety
lighting automatically. The results of both automatic and
manual tests must be recorded. At the same time, safety
luminaires should be switched on with the general lighting
during normal operation. EATON´s 3-PM-IO modules offer
all these functions in one device in compliance with stan-
dards.
The easily accessible test button offers the advantage that
an interruption of the mains voltage is not necessary to
check the function of the voltage monitoring devices. As a
rule, one of the monitored phases must be enabled without
a test button, which at least leads to a failure of the power
supply of the general lighting and thus to severe disturban-
ces of the operational processes.
Ordering details
type
Description
Order No.
3-PM-IO Module
Phase monitor / light switch interrogation Bus
module for DIN rail mounting
40071361670
Technical description
Dimensions LxHxT:
107x90x58 mm³
Weight:
0,2 kg
Installation:
DIN Rail Snap on
Degree of protection:
IP20
Protection class:
II
Ambient temperature:
-10°C…+40°C
Storage temperature:
-20°C…+65°C
Relative humidity:
10%….95% no condensation
Air pressure:
795….1080 hPa
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage Input (Mains):
UN = 220.…240 V AC
Switching thresholds:
≤ 60% UN OFF
≥ 85% UN ON
Rated voltage:
19.2….30 V DC
Rated current:
0,25A
Rated frequency:
50 or 60 Hz
Degree of pollution
2
Overvoltage category Input (Mains):
III
Overvoltage category 24V supply:
II
Rated insulation voltage:
264 V
Heat dissipation:
< 6.6 W
RS 485 Bus connection:
≤ 30 V SELV
Polarity:
polarity independent
Bus Topologie:
Line
Cable type:
Z.B. IY(ST)Y 4x2x0,8mm
Maximum cable lenght:
1200m
Terminating resistor:
120Ω (bridge between terminals B1 and B2)
Terminals Connection cross-sections:
0.2-2.5 mm² rigid/flexible
IMPORTANT NOTE
Inputs 6 to 8 report a power failure which is forwarded to
the visualisation (HMI, WEB, VisionGuard) with the destina-
tion specified in the test logbook. Inputs 1 to 5 are used to
query the light switch for general lighting and do not signal
a power failure.