Mounting- and Operating Instruction Eaton LoadStar-S JSB
40071860396 March 2021 www.ceag.de
16.3. Configure basic settings table (login = untrained specialist)
19
Icon General set-
tings
Actuate
20
Icon System Set-
tings
Actuate
21
ACU Bus ID: Enter ID number 1 to 120
Safety power source: Enter 0 to 65535
22
Icon Log book
Actuate
23
- ACU Bus ID: 1
With LoadStar-S
devices, substa-
tions are connected
to the main station
by subscribing to
the information of
the charging unit
(BCM) from the
main station. For
this the substation
must be connec-
ted to the main
station via the ACU bus. In addition to the BCM information,
IO/3PM-IO modules and the inputs of the ACUs can also be
subscribed to. Several main stations with their substations
can also be connected to the same ACU bus, for example to
use the information of a 3PM IO in all devices. Each device
needs a unique address, the „ACU Bus ID“.
-Safety power source: 0
For the unique assignment of devices when connected to
the VisionGuard visualization solution, a number must be
assigned to the safety power source. All devices that are
connected to the same safety power source (usually battery)
must use a unique number. The number „0“ has the special
meaning that the device works in „island operation“ and
therefore does not supply any other devices via its safety
power source. The setting range is from 0-65535.
Emergency light run-on time
-Manual override
-selective emergency light
-function test according to S1S2 on
-Name:
-Information: