50
Mounting- and Operating Instruction Eaton LoadStar-S JSB
40071860396 March 2021 www.ceag.de
17 General product description LoadStar-S
17 General product description LoadStar-S
The LoadStar-S central battery system reliably supplies
safety and escape sign luminaires with power (230V
AC/220 V DC), automatically checks itself and monitors
each of the connected CG-S luminaires (up to 20 per circuit)
simply via the supply line. Thanks to STAR technology, the
switching mode of each connected CG-S luminaire can be
freely programmed via the control section of the central
battery system within a 50 or 60 Hz grid. This means that
mixed operation of maintained light, switched maintained
light and non-maintainedy light is possible in one and the
same circuit - and that without an additional data line! The
colour touch display in 4.3“ or 7“ version with non-volatile
program memory monitors and controls the central battery
system via the ACU module. All functions of the connected
devices and emergency lights are automatically checked
and reported.
The LoadStar-S uses the search functions to find all lights
and I/O modules and automatically detects all modules and
system-related lights addressed during installation. The
VisionGuard monitoring software can be connected via an
Ethernet interface.
LoadStar-S types
Depending on the requirements on site, different system
configurations are used. These standardized configurations
have designations, e.g.:
LoadStar-S 20
For operation with max. 20 circuit modules SKU.1 CG-S
with 88 circuit. Up to 6 substations can be supplied with
battery current and mains current (up to 6 substations
1-phase, up to 2 substations 3-phase).
LoadStar-S 20C6, LoadStar-S 12C4
for operation with max. 12 or 20 circuit modules SKU.1
CG-S with 68 respectively 48 circuits.
LoadStar-S US 7
For operation with max. 7 circuit modules SKU.1 CG-S.
With these substations, the charging technology of the
connected battery emergency power supply is not requi-
red; the battery and mains power supply is provided via the
LoadStar-S system.
LoadStar-S US-S SOU2, US-S SOU1
For operation with max. 1 or 2 circuit switching modules
SOU CG-S. The touch screen is not required for these sub-
stations. The battery is supplied by the LoadStar-S system,
the mains is supplied via the sub-station of the general
power supply (rental power supply).
All devices and substations have a modular design. Charging
technology, switching technology and monitoring technolo-
gy form units that work independently of each other so that
interactions can be ruled out. The modular design and pre-
assembled cabinet assemblies ensure flexible, high-quality
handling. The protective objective of the safety lighting
systems is to supply the connected safety lighting in the
event of a failure of the general power supply. From the
primary backup power source. Furthermore, an important
function of the safety lighting system is to ensure the ope-
rational readiness of all connected Safety and escape sign
luminaires with automatic monitoring.
LoadStar-S 20
LoadStar-S 12C4
LoadStar-S 20C6
LoadStar-S US SOU2
LoadStar-S US SOU1
396
230
685
230
535
396