
Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1
www.eaton.com/ePDU
84
PDU.PowerSummary.iName
String[31]
Unit friendly name.
-
RW
PDU.PowerSummary.iPartNumber
String[15]
Part Number.
-
RO
PDU.PowerSummary.iProduct
String[63]
Product Name.
-
RO
PDU.PowerSummary.iReferenceNumber
String[31]
Technical Reference of firmware.
-
RO
PDU.PowerSummary.iSerialNumber
String[15]
Serial Number.
-
RO
PDU.PowerSummary.iVersion
String[15]
F/W Version.
-
RO
PDU.PowerSummary.OverTemperature[3].Threshold
Parameter
Threshold
d°K
RW
PDU.PowerSummary.OverTemperature[4].Threshold
Parameter
Threshold
d°K
RW
PDU.PowerSummary.PDUType
Constant
Feature Topology of the PDU:
0: Unknown
1: SW (Switched)
2: MO (Metered Outlet)
3: MA (Managed)
4: MI (Metered Input)
5: IL (In-Line Metered))
-
RO
PDU.PowerSummary.PresentStatus.CommunicationLost
AlarmL1
Communication intra modules have failed.
-
RO
PDU.PowerSummary.PresentStatus.OverTemperature
AlarmL1
0 : No threshold trigged
1 : Warning low threshold trigged
2 : Critical low threshold trigged
3 : Warning high threshold trigged
4 : Critical high threshold trigged
-
RO
PDU.PowerSummary.Temperature
Measure
Internal Temperature.
d°K
RO
PDU.PowerSummary.Time
Measure
Unix timestamp that is refreshed from the RTC.
s
RW
PDU.PowerSummary.Timer
Measure
Time elapsed since the 1st start of the device.
s
RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name
Type
Description
Unit
Access
Table 9. System CLI Objects
XML Object Name
Access
right
Type
Description
Access
Default Value
System.Bootloader.iVersion
admin
String:15
RO
""
System.Bootloader.Mode
superadmin
BootMode
0: Normal
1: Upgrade
2: Passthru
3: ATE
4: Bootstrap
RW
0
System.Contact
admin
String:31
RW
""
System.DaisyChain.Count
admin
Integer0to65535
RO
1