
Maintenance and Alarms
Eaton ePDU G3 Operation Manual P-164000277—Rev 1
www.eaton.com/ePDU
140
2
211400
ePDU Input 1 Over Current Critical
The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2
212000
ePDU Input 1 Voltage No Threshold
No section voltage threshold has been triggered.
2
212100
ePDU Input 1 Low Voltage Warning
The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2
212200
ePDU Input 1 Low Voltage Critical
The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2
212300
ePDU Input 1 Over Voltage Warning
The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2
212400
ePDU Input 1 Over Voltage Critical
The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2
213000
ePDU Input 1 Frequency OK
Utility frequency is within the +/- 3 Hz of Nominal
frequency.
2
213100
ePDU Input 1 Frequency Out of Range
Utility frequency greater or less than +/- 3 Hz of
Nominal frequency.
2
214000
ePDU Input 2 Current No Threshold
No section current threshold has been triggered.
2
214100
ePDU Input 2 Low Current Warning
The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2
214200
ePDU Input 2 Low Current Critical
The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2
214300
ePDU Input 2 High Current Warning
The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2
214400
ePDU Input 2 High Current Critical
The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2
215000
ePDU Input 2 Voltage No Threshold
No section voltage threshold has been triggered.
2
215100
ePDU Input 2 Low Voltage Warning
The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2
215200
ePDU Input 2 Low Voltage Critical
The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2
215300
ePDU Input 2 High Voltage Warning
The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2
215400
ePDU Input 2 High Voltage Critical
The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2
216000
ePDU Input 2 Frequency OK
The frequency is not out of range.
2
216100
ePDU Input 2 Frequency out of +/- 3 Hz
tolerance
The frequency is out of range.
Table 12. ePDU and User Alarms and Events (Continued)
Type Code
Identification and
Index Code
Alarm or Event
Description