
Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1
www.eaton.com/ePDU
75
PDU.Gang[x].Pole[1].ReactivePower
HideMeasure
Reactive Power provided by the pole.
dVA
R
RO
PDU.Gang[x].Pole[1].Statistic[4].Energy
HideMeasure
Energy counter since last reset. As it is reset to 0, the
related timestamp is updated with the current RTC value.
Wh
RO
PDU.Gang[x].Pole[1].Statistic[5].Energy
HideMeasure
Energy counter since last reset. When it is reset to 0 then
at the same time the related timestamp is updated with
the current RTC value.
Wh
RO
PDU.Gang[x].Pole[1].Voltage
HideMeasure
Voltage Measured on the pole.
cV
RO
PDU.Gang[x].Pole[2].ActivePower
HideMeasure
Active Power provided by the pole.
dW
RO
PDU.Gang[x].Pole[2].ApparentPower
HideMeasure
Apparent Power provided by the pole.
dVA
RO
PDU.Gang[x].Pole[2].Current
HideMeasure
Current Power provided by the pole.
mA
RO
PDU.Gang[x].Pole[2].PeakFactor
HideMeasure
Crest factor of the current provided by the pole.
m%
RO
PDU.Gang[x].Pole[2].PhaseID
Constant
Phase number that is connected to the pole: 1, 2, or 3.
-
RO
PDU.Gang[x].Pole[2].PowerFactor
HideMeasure
Ratio of active power / apparent power provided by the
pole of the breaker or outlet section.
m%
RO
PDU.Gang[x].Pole[2].ReactivePower
HideMeasure
Reactive Power provided by the pole.
dVA
R
RO
PDU.Gang[x].Pole[2].Statistic[4].Energy
HideMeasure
Energy counter since last reset. As it is reset to 0, the
related timestamp is updated with the current RTC value.
Wh
RO
PDU.Gang[x].Pole[2].Voltage
HideMeasure
Voltage Measured on the pole.
cV
RO
PDU.Gang[x].PowerFactor
Measure
Ratio of active power / apparent power provided by the
breaker or outlet section.
m%
RO
PDU.Gang[x].PresentStatus.OverCurrent
AlarmL1
0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
-
RO
PDU.Gang[x].PresentStatus.OverVoltage
AlarmL1
0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
-
RO
PDU.Gang[x].PresentStatus.SwitchOnOff
AlarmL1
-
RO
PDU.Gang[x].PresentStatus.Tripped
AlarmL1
0 : Breaker closed
1 : Breaker tripped (or open)
-
RO
PDU.Gang[x].ReactivePower
Measure
Reactive Power provided by the breaker/section. For a
double pole breaker, the reactive power for the two poles
is combined.
dVA
R
RO
PDU.Gang[x].Statistic[3].Current
Measure
Current peak consumption since last reset.
As it is reset to 0, the related timestamp is updated with
the current RTC value.
When a value higher than the stored value is detected, the
stored valued is overwritten.
mA
RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name
Type
Description
Unit
Access