
Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1
www.eaton.com/ePDU
79
PDU.Input[1].Statistic[5].Reset.Energy
Measure
Energy saved at the instant the user resets the stat.
Wh
RO
PDU.Input[1].Statistic[5].Reset.Time
Measure
Timestamp saved at the instant the user resets the stat.
s
RO
PDU.Input[1].Type
Constant
List types of PDU Input plugs.
-
RO
PDU.Input[2].ActivePower
Measure
Active Power Measurement.
It's the cumul of 1 or 3 phase measures.
dW
RO
PDU.Input[2].ApparentPower
Measure
Apparent Power Measurement.
It's the cumul of 1 or 3 phase measures.
dVA
RO
PDU.Input[2].ChangedStatus.FrequencyOutOfRange
Timestamp
s
RO
PDU.Input[2].Frequency
Measure
Frequency Measurement.
dHz
RO
PDU.Input[2].Mode
Constant
Wiring Mode
0: Wye Measuring
1: Delta Measuring
2 : Wye Current and Delta Measuring
-
RO
PDU.Input[2].Phase.Count
Constant
Number of phase managed by the Input module.
-
RO
PDU.Input[2].Phase[x].ActivePower
Measure
Active Power Measurement.
dW
RO
PDU.Input[2].Phase[x].ApparentPower
HideMeasure
Apparent Power Measurement.
dVA
RO
PDU.Input[2].Phase[x].ChangedStatus.OverCurrent
Timestamp
Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s
RO
PDU.Input[2].Phase[x].ChangedStatus.OverVoltage
Timestamp
Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s
RO
PDU.Input[2].Phase[x].Current
Measure
Current Measurement.
mA
RO
PDU.Input[2].Phase[x].OverCurrent[1].Threshold
Parameter
mA
RW
PDU.Input[2].Phase[x].OverCurrent[3].Threshold
Parameter
mA
RW
PDU.Input[2].Phase[x].OverCurrent[4].Threshold
Parameter
mA
RW
PDU.Input[2].Phase[x].OverVoltage[1].Threshold
Parameter
cV
RW
PDU.Input[2].Phase[x].OverVoltage[2].Threshold
Parameter
cV
RW
PDU.Input[2].Phase[x].OverVoltage[3].Threshold
Parameter
cV
RW
PDU.Input[2].Phase[x].OverVoltage[4].Threshold
Parameter
cV
RW
PDU.Input[2].Phase[x].PeakFactor
Measure
Crest factor of the current provided by the phase.
m%
RO
PDU.Input[2].Phase[x].PercentLoad
Measure
Percent load consumed on the phase. It is the ratio :
current consumed / the nominal current of the PDU.
%
RO
PDU.Input[2].Phase[x].PhaseID
Constant
Phase ID identifier depending of the wiring :
1 : Line 1 to Neutral
2 : Line 2 to Neutral
3 : Line 3 to Neutral
-
RO
PDU.Input[2].Phase[x].PowerFactor
HideMeasure
Ratio of active power / apparent power provided by the
phase.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m%
RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name
Type
Description
Unit
Access