Input data: Mode, S1 – S8
49
09/10 MN05013007Z-EN
Input data:
Mode, S1 – S8
Attribute ID: 3
The cyclic data transfer between DeviceNet master and the
EASY222-DN slave is provided by the input data byte 0, 1
and 2.
Table 7:
Byte 0 to 2: input data, mode
The master reads the following data from bytes 0, 1 and 2:
Table 8:
Byte 0: Operating mode
0 = status "0“ 1 = status "1"
Example:
Value 21
hex
= 00100001
bin
:
"easy" is in RUN mode and operates with input delay
Byte
Meaning
Value
0
Operating mode scan
1
Scan status of the easy outputs S1 to
S8
2
Not used
00
hex
easy identification
Bit
7
6
5
4
3
2
1
0
STOP/RUN
without input delay
0
0
0
1
0
0
0
0/1
with input delay
0
0
1
0
0
0
0
0/1