Read/write function blocks
79
09/10 MN05013007Z-EN
Remember this feature when uploading, downloading or
comparing “easy” circuit diagrams with easySoft.
When downloading from the PC the latest version of the
“*.eas” is overwritten.
The comparison shows that the circuit diagrams are not
identical.
Table 31:
Byte 0: control byte
Example:
Value 80
hex
= 1000000
bin
:
The reference value will be written to the selected timing
relay and appears in the parameter menu.
Setting the reference value
(byte 1 and byte 2)
These two bytes determine the reference value of the
counter relay. The reference value can be set within the
range from 0 to 9999
dec
. To do so, you must convert the
required decimal into the equivalent hexadecimal value and
then split it up into the low-byte and high-byte.
Example:
Reference value = 4318
dec
= 10DE
hex
:
Low-value: DE
hex
High-value: 10
hex
Meaning
Bit
7
6
5
4
3
2
1
0
Not used
0
0
0
0
0
0
Does not appear in the parameter
menu
1
Appears in the parameter menu
0
Edit
1