Read/write function block data
215
09/10 MN05013007Z-EN
Table 130:
Index 0 – Bit IO
The data in the following table is shown in the Motorola
format although it is actually transferred in Intel format.
Table 131:
Index 2 – 5, Parameter channels A – D
Example
The channel A parameters of year time switch HY14 are to
be written.
Bit 7 6 5 4 3
2
1
0
FB output Data 3
– – – – –
–
–
Q
1)
1) Status 1 if the switch-on condition is fulfilled.
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 2
Date 1
ON
y6
y5
y4
y3
y2
y1
y0
m3
m2
m1
m0
d4
d3
d2
d1
d0
Year
Month
Day
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 4
Date 3
OFF
y6
y5
y4
y3
y2
y1
y0
m3
m2
m1
m0
d4
d3
d2
d1
d0
Year
Month
Day
d4 ... d0: Day (1 .. 31), m3 ... m0: Month (1 .. 12), y6 ... y0: Year (0: 2000 .. 99: 2099)
Index 2 – 5, Parameter channels A – D
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 2
Date 1
ON
0
0
0
0
0
1
1
0
1
1
0
0
1
1
1
0
Year
Month
Day
Switch-on time:
Day = 14 = 0E
hex
= 000
0 1110
bin
Month = 6 (June) = 06
hex
= 0000
0110
bin
Year = 20
03
= 03
hex
= 0
000 001
1
bin
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 4
Date 3
Summary of Contents for EASY222-DN
Page 10: ...Contents 6 09 10 MN05013007Z EN...
Page 34: ...30 09 10 MN05013007Z EN...
Page 258: ...254 09 10 MN05013007Z EN...
Page 274: ...Glossary 270 09 10 MN05013007Z EN...