Read/write image data
159
09/10 MN05013007Z-EN
Read local inputs: IW0
This command string enables you to read the local inputs of
the easy800/MFD. The relevant input word is stored in Intel
format.
Telegram structure
Table 81:
Byte 4 to 5: Data 1 to 2
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID: Read
91
–
0
Response:
Read successful
–
C2
Command rejected
–
C0
0
1
Len
02
02
1
2
Part no.
01
01
2
3
Index
00
00
3
4
Data 1 (Low Byte)
00
4
5
Data 2 (High Byte)
00
5 – 6
6 – 7
Data 3 – 4
00
00
Data 1
Bit
7
6
5
4
3
2
1
0
I1
0/1
I2
0/1
…
…
I8
0/1
Data 2
Bit
7
6
5
4
3
2
1
0
I9
0/1
I10
0/1
…
…
I16
0/1