Control commands for easy600
66
09/10 MN05013007Z-EN
Timing relays, counter relays, timer switch,
analog value comparator
The following command reads the logic state of all timing
relays, counters, time switches and analog value compara-
tors.
Telegram structure
Byte
Meaning
Value (hex), sent by
Bit
M
S
Master
Slave
7 6 5 4 3 2 1 0
Attribute ID
Read
5E
–
0 1 0 1 1 1 1 0
0
Response
Read successful
–
C2
1 1 0 0 0 0 1 0
Command
rejected
–
C0
1 1 0 0 0 0 0 0
0
1
Status of timing
relay
00
1
2
Counter relay status
00
2
3
Time switch status
00
3
4
Analog value
comparator status
00
M