Read/write function block data
203
09/10 MN05013007Z-EN
Table 116:
Operand overview
Index
(hex)
Operand
Reading
Writing
00
Bit IO,
x
01
Mode,
x
02
Setpoint: –32768 to +32767
I1
x
c
1)
03
Actual value: –32768 to +32767
I2
x
c
1)
04
Proportional Gain
[%], Value range: 0 to 65535
KP
x
c
1)
05
Reset time [0.1 s], Value range: 0 to 65535
TN
x
c
1)
06
Rate time [0.1 s], Value range: 0 to 65535
TV
x
c
1)
07
Scan time = Time between function block calls
Value range: 0.1s to 6553.5s
If 0 is entered as the value, the scan time will be deter-
mined by the program cycle time.
TC
x
c
1)
08
Manual manipulated variable, value range:
–4096 to +4095
MV
x
c
1)
09
Manipulated variable
QV
x
• Mode: UNI, value range: 0 to +4095 (12 bit)
• Mode: BIP, value range: –4096 to +4095 (13 bit)
1) The value can only be written if it is assigned to a constant in the program.
h
The data for index 2 to 9 is transferred as a 32-bit value in
Intel format (Data 1 – Low Byte to Data 2 – High Byte).