7 Technical Data
7.2 Specific rated operational data
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
163
7.2.2 DC1-S2…device series
Size
Symbol
Unit
4D3
7D0
011
Rated operational current
I
e
A
4.3
7
10.5
Overload current for 60 s every 600 s
i
l
A
6.45
10.5
15.75
Assigned motor output
at 230 V, 50 Hz
P
kW
0.37
0.75
1.1
at 220 - 240 V, 60 Hz
P
HP
0.5
1
1.5
Power side (primary side):
Number of phases
single-
phase
single-
phase
single-
phase
Rated operating voltage
U
LN
V
200 - 10 % - 240 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current)
I
LN
A
6
9.3
14
Minimum braking resistance
R
B
Ω
–
–
100
Switching frequency (pulse frequency)
Default Setting
f
PWM
kHz
8
8
8
Setting range
f
PWM
kHz
4 -32
4 -32
4 -32
Maximum leakage current to earth
(PE), at U
LN
: 240 V, without motor
I
PE
mA
4.8
4.8
4.8
Efficiency
η
0.94
0.96
0.95
Heat dissipation
At I
e
(150 %)
P
V
W
45.75
63
103.4
During no-load running, standby
(locked, without fan)
P
V
W
3.07
3.07
4.51
Fan, built-in
✓
✓
✓
Construction size
FS1
FS1
FS2
Summary of Contents for DC1-S1011NB-A20CE1 1