3 Installation
3.3 Mounting
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
49
3.3.1 Mounting position
DC1-S… series variable frequency drives are designed to be mounted
vertically. The maximum permissible inclination is 30°.
Figure 20: Mounting position
3.3.2 Cooling measures
To ensure that there is sufficient air circulation, appropriate thermal
clearances must be maintained, with these clearances depending on the size
of the specific variable frequency drive.
≦ 30º
≦ 30º
≦ 30º
≦ 30º
Figure 21: Clearances for air cooling (left: IP20; right: IP66)
→
The variable frequency drives can be mounted side by side
without any lateral clearance between them.
b
c
a
c
a
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
c
a
c
REV
FWD
0
ON
OFF
PWR
b
a