6 Parameter structure
6.4 Control signal terminals
128
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
6.4.2.2 P-12 = 1: digital setpoint value, 1 operating direction
Table 34: P-12 = 1: digital setpoint value, 1 operating direction
The setpoint value is set using the keypad = digital setpoint value. The arrow
buttons are used to adjust the setpoint value.
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0
START
UP
DOWN
No function
1
Not permissible
2
START
UP
DOWN
Select DIG REF/f-Fix1
3
START
UP
EXTFLT
DOWN
4
START
UP
Select DIG REF/AI1 REF
AI1 REF
5
Not permissible
6
START
No function
EXTFLT
Select DIG REF/f-Fix1
7
START
Select Quick
‐
dec
EXTFLT
Select DIG REF/f-Fix1
8
Not permissible
9
Not permissible
10
Not permissible
11
Not permissible
12
Not permissible
13
START
No function
EXTFLT
No function
14
Not permissible
15
START
Select f-Fix/DIG REF
Select Fire Mode/Normal OP
Select f-Fix4/f-Fix2
16
START
Select f-Fix4/DIG REF
Select Fire Mode/Normal OP
No function
17
START
Select DIG REF/f-Fix4
Select Fire Mode/Normal OP
No function
Summary of Contents for DC1-S1011NB-A20CE1 1
Page 4: ......