6 Parameter structure
6.2 Resetting Parameters (RESET)
122
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
6.2 Resetting Parameters (RESET)
Table 30: Resetting parameters (RESET)
6.3 Extended parameter set
Table 31: Enabling and disabling access to the extended parameter set
Commands
Description
Reset to default settings
+
+
Press the
▲
and
▼
and STOP buttons and hold them down for two seconds.
→
All parameters will be restored to their default settings.
The display will show
P-dEF
.
Resetting after a fault
Press the
STOP
button to reset a fault message.
The display will show
StoP
.
Commands
Description
Enabling access to the extended parameter set
Press the
OK
button and hold it down for two seconds in
order to access the parameter interface
→
The display will show the parameter that was last
used.
Use the
▲
and
▼
buttons to select parameter P-14
Press the
OK
button.
Use the
▲
and
▼
buttons to enter the password set with
P-37 (default setting: 101)
Press the
OK
button to confirm
→
The extended parameter set (parameters > P-14 and
display values P00-…) will now be available.
Disabling access to the extended parameter set
Use the
▲
and
▼
buttons to set a value for P-14 that does
not match the password (P-37).
Press the
OK
button to confirm
→
Only the “basic parameters“, P-01 to P-14, will be
accessible now.
→
The extended parameter set (default setting for P-37 = 101)
contains parameters P-01 to P-55. Additional parameters P-60 to
P-68 can be configured for specific applications. The corres-
ponding password is 201 in parameter P-37 (value of P37 + 100).