79
8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Line selection (line 1 / 3) with
Select a relay in line 1 with
Line 4 shows the current relay status
Select between “dropped out” and
“picked up” in line 3 (e.g. for test pur-
poses) with
Relay: 1
Status:
picked up
The current charge and battery status is
displayed (see screenshot opposite):
U: present battery voltage
I: present charge current / discharge
current
T: temperature in the battery compart-
ment (from temperature sensor in-
stalled in it)
BT: last attainable operating duration, in
hours
Displays the current battery capacity in line
3 based on 3.11 “Charger setup”
Line 4 only displays messages when a
malfunction occurs. Selection can be made
with
if more than one fault is present
<ok>
Menu 1.9:
U=213.0 V
I=+ 0.2 A
T= +18.0°C BT:03:00h
Batt capacity: 95%
Message line
<ok>
Menu 1.8:
<ok>
Menu 1.7:
<ok>
Menu 1.6:
Start functiontest
Start durationtest
Cancel durationtest
Sum failure info
Circuit state
Luminaire state
etc.
SKU 2/1
circuit:1
....5.....10.....15....2
—-
————————
-
Luminaire name
DLS module external 2
1 2 3 4 5 6 7 8
DLS/TLS Text
TLS module external 3
1 2
DLS/TLS Text
Submenu 1.7 depends on the device
(DLS/3PhW or TLS) that is being addressed
by the selection in the menu.
Select an address with
Line 2/3 shows the current status of
the signal outputs of the external mod-
ule or a current fault message. Line 4
shows the device name (see “4 DLS/
TLS Setup”).
Note:A 3-phase monitor status (L1...L3)
is shown when the external DLS/3PhW
module has been configu-red as a
combined DLS/3-phase monitor.
Switch status/Phase Off
Switch status/Phase On
Select input field/line with
Select SKU or circuit with
Line 3 shows the current settings of
the luminaire addresses (1 ... 20) in the
selected circuit:
Luminaire is off (Item 1)
Luminaire is on (Item 2)
Luminaire failure (Item 3)
– no luminaire set up (Item 4)
(see “6 Luminaire Setup”)
Select a luminaire (line 2) with
Line 4 shows the luminaire name
(see “6.2 Text assignments”)
Start functiontest
Start durationtest
Cancel durationtest
Sum failure info
Circuit state
Luminaire state
DLS/TLS/3PhW state
Charging/Bat. state
Relay state
Substation state
Start functiontest
Start durationtest
Cancel durationtest
Sum failure info
Circuit state
Luminaire state
DLS/TLS/3PhW state
Charging/Bat. state
Relay state
Substation state
DLS+3Phase monit. 1
1 2 3 4 5 L1 L2 L3
DLS/TLS Text
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 1
Start functiontest
Start durationtest
Cancel durationtest
Sum failure info
Circuit state
Luminaire state
DLS/TLS/3PhW state
Charging/Bat. state
Relay state
Substation state
Selection of
menu options
with the keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return to
the previous
menu (any
changes
entered are
saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Start functiontest
Start durationtest
Cancel durationtest
Sum failure info
Circuit state
Luminaire state
DLS/TLS/3PhW state
etc.
Note:
See also menu option 3.8 “Relay assign-
ments” in menu 3 “Basic settings”.
Circuit state
Luminaire state
DLS/TLS/3PhW state
Charging/Bat. state
Relay state
Substation state
<ok>
Menu 1.10:
Device address 1
Status message
Failure info
Device name
Select a station in line 1 with
Line 2 shows the current operation status
of the chosen station ZB-S by Multi
Master Mode M3.