84
8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
<ok>
Menu 3.9:
Select the system or fault messages which
activate the buzzer in the switch cabinet.
A standard setting according to DIN VDE
(see Appendix B) can be selected using
the “Load defaults” option at the end of
this menu.
Highlight the events with
Select buzzer “On” (
) or buzzer
“
O
ff
”
(no
) with keys
Finish and return to Menu 3 with
<Menu>
ote:
N
The buzzer’s maintained signal
tone (after the onset of an event
specified here) can be silenced by
pressing any key.
ote:
N
“Brightness (on)” is the display setting when the display is active (press any
key to activate). If no key is pressed within 180 seconds, the controller switch-
es the display to passive (dimmed backlighting) “Brightness (off)”.
The above settings may make the display unreadable (e.g. depending on the
ambient lighting).
(The active display setting can be changed at any time from the main screen
by pressing <ok> and a key (for contrast) or (for brightness) of the active LCD
display.)
Setting contrast and brightness (back-
lighting) for the LCD display of the CU
CG-S control module.
Line selection (2 to 4) with
Set the values (0 to 100%) with keys
Finish and return to Menu 3 with
<Menu>
<ok>
Menu 3.10:
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
etc....
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
etc....
Display setting
Contrast 50%
Brightness on:100%
Brightness off: 10%
Buzzer assignment
Mains operation
Mains failure
Mains failure UV
Charge fault
Circuit fault
Luminaire fault
Sum failure
Deep discharge protection
ISO failure
Function test
Battery duration test
DB-FÜB
Gerätestörung
Load defaults
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 3
Language
Date & time
Functiontest
Durationtest
Delay time mains
return
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
Charger setup
Printer setup
Relay module setup
Webserver setup
Timer setup
Substation setup
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Entries about the switch cabinet equip-
ment
Select line 2, 3 and 4 with
Change the settings with
– Line 2: Toggle between
“installed” / “not installed”
(charging module LT.1 2,5 A or BCM)
– Line 3: Number of boosters = 1 ... 10
(charge booster 2,5 A)
– Line 4: Battery capacity in Ah can be
selected between 5 and 999
short key press in increments of 1;
long key press in increments of 10.
Finish and return to Menu 3 with
<Menu>
<ok>
Menu 3.11:
Relay setup
Buzzer setup
Display setup
Charger setup
etc....
Important NOTE
These details must be entered exactly or the emergency
lighting system controller may fail.
Caution:
The specification for the number of charging
boosters only applies to 2.5 A charging boosters. If a
BCM is mounted, only specification of the number of 2.5
A charging boosters is permitted. If no 2.5 A charging
boosters are installed, the specification for „number of
boosters“ must be „0“.
Exception:
If a CM 3.4 A charging module is installed as
a replacement for a 2.5 A charging booster then this must
also be counted. Observe here that the address of the CM
3.4 A charging module is set to „00“.
Charger setup
installed
Number of boosters 4
Batt.capacity 80Ah