Appendix B: VDE requirements for telecommunication contacts and buzzers
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
NOTE:
Comply with the national regulations and guidelines for
indicating and signalling when using a remote switch or
remote indicator for emergency lighting systems.
Contact assignment:
C0/14: NO
C0/24: NO
C0/34: NO
C1/44: NO
C0/12: NC
C0/22: NC
C0/32 : NC
C1/54: NO
Note:
NO = normally open
NC = normally closed
The device has 5 floating signalling contacts (relay outputs)
and one buzzer inside the device.
Signal contacts K3, K4, K5 can be freely parameterised, for
each: 1 x changeover contact 1 x 24V; 0.5A
Relay contacts K1 (external buzzer) and K2 (technical swit-
ching cabinet ventilation) have fixed assignments.