29
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
4.2 Product Description
The Central Battery System ZB-S with the new START
technology is a logical successor to the wellproven
Central Battery System ZB 96. STAR stands for:
SWITCHING TECHNOLOGY ADVANCED REVISION
The main benefits of this technology include the fact
thatwithin a final circuit, the switching modes
O
O
Non-maintained light (Emergency lighting is switched
on when the main lighting fails or when a function
test or operating duration test is initiated manually or
automatically)
O
O
Maintained light and (Emergency lighting is always on)
O
O
Switched maintained light (as non-maintained light with
emergency lighting controlled by switch queries, e. g.
from external DLS-modules) can be implemented in
hybrid mode for each emergency luminaire.
O
O
each safety and EXIT luminaire can be programmed
without an extra data cable,
O
O
the switching modes can be later modified without
the need to interfere in the existing luminaire
installation.
The functions of the emergency luminaires are defined
with a user-friendly parameter setup system.
The use of CG-S type ballasts/modules is a requirement.
All settings are stored in a nonvolatile memory and so are
not lost even in a total shutdown situation (230V mains
and battery supply).
Parameter settings and the names of circuits, luminaires
and DLS/TLS-modules as well as test log entries can
also be stored on a memory card. As well as archiving,
this also allows (optional) external parameter setting and
transfer to control modules of the ZB-S system.
Maintenance-free and closed batteries according to
EN 60896-2 supply the power needed to operate the
emergency lighting if the 230V mains supply should fail.
During normal operation, the ZB-S system monitors the
charge status of the batteries and charges them up gently
if required.
The system ZB-S is designed and manufactured in
compliance with the following EC directives:
O
O
Low-voltage Directive 2006/95/EG
O
O
Directive 2004/108/EG on electromagnetic compatibility
National (DIN-), European (EN-) and international (IEC-)
standards which the system complies will be found in the
system´s CE Certificate of Conformity.
4.3 Operation Modes
Different system configurations are used depending
on the requirements of the site. These standardised
configurations have names like
ZB-S/26 or ZB-S/18
for operation with up to 26 or 18 SKU CG-S modules (resp
CG) with 80 or 68 circuit terminals. Up to 6 substations
US-S can be supplied with battery or mains power (up to
6 substations 1-phase, up to 2 substations 3-phase).
ZB-S/LAD
These are designed as charging and monitoring units
for the mains and battery supply to a large number of
substations US-S. Up to 4 circuits can be supplied and
controlled.
ZB-S/10C, ZB-S/10C6, ZB-S/18C6, ZB-S/26C6, ZB-
S/10C3, ZB-S/18C3, ZB-S 2C3
for operation with up to 10 or 18 SKU CG-S modules
(resp. CG) with 40, 56 and 60 circuit terminals.
US-S/36, US-S/28, US-S/21, US-S/13, US-S/5
for operation with up to 5, 13, 21, 28 or 36 SKU CG-S
modules(resp. CG) with 20, 24, 26, 52 and 80 circuit
terminals. These substations do not have the charging
technology of the connected battery standby supply; the
battery and mains supply is provided by the ZB-S system.
US-S/SOU2, US-S/SOU1
for operation with max. 1 or 2 circuit switching modules
SOU CG-S with 4 or 2 circuit terminals With these
substations the CU CG-S control unit is not required.
Battery supply is via the ZB-S system, mains supply is
via the sub-distributor of the general power supply (rental
current feed).
ESF-30/13S, ESF-E30/28S
Mains distribution board with circuit integrity of 30
minutes in case of fire for operation with up to 13 or 28
SKU CG-S modules with 40 or 60 circuit terminals.
US-S ESF30 13-P, US-S ESF30 28-P
Mains distribution board with circuit integrity of 30
minutes in case of fire for operation with up to 13 or 28
SKU CG-S modules with 40 or 60 circuit terminals.
US-S ESF30 SOU5, US-S ESF30 SOU3, US-S ESF30
SOU2, US-S ESF30 SOU1
Mains distribution board with circuit integrity of 30
minutes in case of fire for operation with 5, 3, 2 or 1 SOU
CG-S 2 x 4 A modules with 10, 6, 4, or 2 circuits.
All devices and substations are constructed modularly. The
technologies of charging, changing-over and of monitoring
form a unit working undependent from each other, so that
interactions can be excluded.
Due to the modular construction and the pre-configured
modules a flexible and high quality handling is ensured. The
objective of the emergency lighting system is to supply the
connected emergency luminaires when the main lightings
fails. Another important function of the system is to secure
the function standby of all connected emergency and EXIT
luminaires by an automatic monitoring.