32
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Control inputs
The 24V analog inputs Z1 ... Z4 are to control the external control panels, a programmable trip of operational functions (e.
g. bloc / release system, manual reset, etc.) is given.
Optional inputs Z1 - Z4
Z1
Z2
Z3
Z4
Comments:
No function
-
Factory settings
Switch
Level triggered (by use of a switch)
24VDC = ON
0V = OFF
Used as a switch and switches the circuit
or the luminaires with “S” function�
Switch inverted
Manual reset
Edge triggered (by use of a push switch)
LOW
HIGH
To reset the circuit arrangement
”manual reset“�
Deep discharge receipt
To acknowledge a deep discharge
protection�
Start functiontest
Start a function test�
Start durationtest
Start a duration test�
Cancel FT/DT
Cancel function test / duration test�
Block device
Block function of mains/emergency
lighting during shut-downs�
Switch-off maintained light
Switch off all luminaires /circuits, which
are programmed as maintained light�
Switch-on non-maintained light
Switch on all luminaires /circuits, which
are programmed as non-maintained light�
Ventilator monitor
Level triggered (by use of a switch)
24VDC = OK
0V = Failure
Sets a sum failure at the potential-free
relay contacts of the control module to the
CG IV relay module and the CGVision, as
long as 0V is present�
Ext� ISO monitor
Ext� Battery monitor
Ext� Monitor
Optional Input
All luminaires on
Optional Input
Level triggered (by use of a push switch)
24VDC = active
AE Szenario aktive
Optional Input
AE Failure
Level trigger:
Edge trigger:
t > 100ms
t > 1s
Z1 to Z4, connection for analogue inputs:
4 freely assignable 24 V analogue inputs, can be
programmed either inverted or non-inverted for
e.g.:
O
O
Start / abort function test
O
O
Start / abort duration test
O
O
Block/release system
O
O
Manual reset
O
O
Switch on / off maintained mode
O
O
Switch on safety lighting as corridor lighting
O
O
Control unit ZB-S componentsand options
as presetting can be called up at any time.
2 relays with common potential, 1 x open contact each
with fixed assignment.
Contact 44 switches an external buzzer on. Contact 54 is
for control of a technical switching cabinet ventilation if
required.