85
8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
<ok>
Menu 3.15:
Timer deactivated/activated
00:00 - 23:59
Mo Tu We Th Fr Sa Su
X X X X X X X
Selection of Timer 1, Timer 2 or Timer
1&2 with the buttons
If there appeares a X under the token
of the weekday, on this day the lumi-
naire operates to programmed time.
Printer setup
Relay module setup
Webserver setup
Timer setup
etc....
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 3
Language
Date & time
Functiontest
Durationtest
Delay time mains
return
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
Charger setup
Printer setup
Relay module setup
Webserver setup
Timer setup
Substation setup
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Buzzer setup
Display setup
Charger setup
Printer setup
etc....
<ok>
Menu 3.12:
Printer setup
installed/not installed
activated/not activated
Is not printer existing or filed via the
Service-Button the following appears:
Printer setup
not installed
A PD3 printer which is parameterised as «not installed» can be logged in (installed
and activated) with the service button (at the printer) at the station.
The possibilities of selection in this menu server for the activation/deactivation of
the logging by the printer and for the log out (deinstallation) during the exchange/
replacement of the paper and the ribbon of the printer.
<ok>
Menu 3.16:
Search substation ...
Group no.: 07
Substation
S1/S2-mode: Slave
S1/S4-mode: -------*
<Menu> finishes the entry and the
following display appears:
Device addresse:01
Version Z410C
ND 00 09 73 72 96 00
Device name
The selection in the second menu serve for the display of the active substations.
Only substations with a programmed group number will be find if not, the message «transmission
failure» appears.
By a selection of «S1/S2-mode: Master - yes» the wohle group can be switched into the mode
«blocked» via the F3-switch of the Master controller. At the Master controller appears the display
«Blocked S1/S2» – at the controllers of the substations appears the message «Blocked LON»
Relay module setup
Webserver setup
Timer setup
Substation setup
etc....
Display setup
Charger setup
Printer setup
Relay module setup
etc....
<ok>
Menu 3.13:
Relay module setup
installed
version CG IV
Is the Relay module located in the mode
«not installed» by pushing the Service
button it can be loged in at the device and
can be switched into the mode «installed».
Charger setup
Printer setup
Relay module setup
Webserver setup
etc....
<ok>
Menu 3.14:
installed
DHCP: ????
IP:???.???.???.???
MASK:???.???.???.???
After connection of the power supply
the webmodule needs approx. 1.5min
for booting. After the booting, the
red LED of the webmodule flashes
slowly.
To log on the webmodule on the CU CG-S control unit, the service pin of the web-
module must be pressed for approx. 1 sec. The menu „webserver setup“ appears
in the display of the control unit of the ZB-S. During the log on procedure the display
shows a lot of question marks. After approx. 3-5 sec. the display shows the network
settings of the webmodule: The webmodule gets automatically activated to the con-
trol unit, which is displayed by the red LED (some seconds) of the control unit and
the webmodule. After 1-2 minutes the procedure is finished and the webmodule is
ready to operate.
Setting options:
S1/S2: Slave or Master
S3/S4: Save or Master or ------
Explanation:
Slave: depends on master
------: does not depend on master