91
8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Menu 5.5:
<ok>
Deactivate module
Search ext. modules
Text assignment
Monitoring mode
DLS/TLS-Assignment
Get new rated value
SKU1/8
circuit:2
per luminaire setup
Maintained light (Batt)
Circuit name
Select line 1, 2, 3 or the input fields in
line 1 with
Successive selection of SKU and (final)
circuit with
Line 4 displays the message “Circuit
text” or a circuit name (see menu 5.3)
Select the settings in line 2 and 3
with keys
Finish and return to Menu 5 with
<Menu>
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 5
Deactivate module
Search ext. modules
Text assignment
Monitoring mode
DLS/TLS-Assignment
Get new rated value
Selection of
menu options
with the keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
ote:
N
The possible settings in line 3 depend
partly on the selection made in line 2
Function keys F1 ... F3 or option inputs Z1 ...
Z4 in line 2 can also be declared as switches
(see menus 3.12 and 3.13 in “Basic settings”).
Switch assignment is not possible unless
these variable elements have been assigned
a switch function!
xx: Module number ( 1 ... )
y: Inputs of the module (e.g. for switch
interrogation) or Switched outputs of TLS
modules
TLS can only be assigned to complete
circuits.
Menu 5.6:
<ok>
On completion of the procedure the CU
CG-S control module returns to Menu 5
“Circuit setup”.
The procedure can be cancelled with the
<ESC> or <Menu> keys.
Main screen
with status line:
Learn currents
Notes:
The “Learn current values” procedure starts when the selection is confirmed with
<ok>. The time taken by the procedure depends on the number of installed circuits.
A reference current value is determined and stored one after the other for all the cir-
cuits with the “Current value monitoring” mode selected (see 5.4 “Monitor mode”)
in battery operation. This value is now used as the basis for malfunction diagnostics
(e.g. luminaire malfunction).
All the desired luminaires must be installed and fully operational!
Deactivate module
Search ext. modules
Text assignment
Monitoring mode
DLS/TLS-Assignment
Get new rated value
see note at menu 3.7
Switch assignment
in line 2
Switch 1
in line 3
Switch 2
Non maintained mode none
Maintained light
(mains)
Maintained light (Batt)
TLS xx/x (Batt)
per luminaire setup
Maintained light (Batt)
TLS xx/x (Batt)
Timer 1
Timer 2
Timer 1&2
Maintained light (Batt)
DLS xx/y
TLS xx/y
DLS xx/x
Maintained light (Batt)
DLSxx/y
TLS xx/y
TLS xx/x
Maintained light (Batt)
DLS xx/y
TLS xx/y
Switch assignment
in line 2
Switch 1
in line 3
Switch 2
Non maintained mode
or
3-phase monitor
none
Maintained light (Batt)
DLS xx/y
TLS xx/y
Maintained light
(mains)
Maintained light (Batt)
TLS xx/x (Batt)
per luminaire setup
Maintained light (Batt)
TLS xx/x (Batt)
3-phase monitor
Timer 1
Timer 2
Timer 1&2
Maintained light (Batt)
DLS xx/y
TLS xx/y
3-phase monitor
DLS xx/x
Maintained light (Batt)
DLSxx/y
TLS xx/y
3-phase monitor
TLS xx/x
Maintained light (Batt)
DLS xx/y
TLS xx/y
3-phase monitor