PROFIBUS I/O Parameters
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
29
Input
2
C440 Temperature
The temperature as seen by the microcontroller (accuracy ~10%)
Input
2
C440 Line Frequency
The line frequency measured by the device (the frequency is displayed in deciHz)
Input
2
C440 Feature Status
Bit Feature
01 = Class Index
00 = Class 10a
01 = Class 10
10 = Class 20
11 = Class 30
2 = Phase loss/imbalance enabled
3 = Ground fault enabled
4 = Auto reset enabled
5 = Remote reset active
8 = DIP switch position 0
9 = DIP switch position 1
10 = DIP switch position 2
11 = DIP switch position 3
12–15 = Reserved
Table 23. C440 Available IO Data for Cyclic Polling, continued
IO
Size (in bytes)
Tag
Description