Configuration Using the PROFIBUS Configuration File
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
17
GND Fault Trip Mode
Motor Insight
0 = Trip on GND fault
1 = Alarm-no-trip—default
Under Current Trip Level
Motor Insight
10–90% of FLA (50) default
Under Current Trip Delay
Motor Insight
1–60 seconds (5) default
Low Power Trip Level
Motor Insight
Setting is in kW x 100
Default value is the minimum value in the range.
Low Power Trip Delay
Motor Insight
1–60 seconds (5) default
High Power Trip Level
Motor Insight
Setting is in kW x 100
Default value is the minimum value in the range.
High Power Trip Delay
Motor Insight
1–60 seconds (5) default
% Current Unbalance Trip Level
Motor Insight
1–30% (15%) default
Current Unbalance Trip Delay
Motor Insight
1–20 seconds (10) default
Under Voltage Trip Level
Motor Insight
170–264 V (216 V) CC441BA, C441BB
323–528 V (432 V) C441CA, C441CB
489–660 V (540 V) C441DA, C441DB
Under Voltage Trip Delay
Motor Insight
1–20 seconds (10) default
Over Voltage Trip Level
Motor Insight
170–264 V (264 V) C441BA, C441BB
323–528 V (528 V) C441CA, C441CB
489–660 V (540 V) C441DA, C441DB
Over Voltage Trip Delay
Motor Insight
1–20 seconds (10) default
% Voltage Unbalance Trip Level
Motor Insight
1–20% (6%) default
Voltage Unbalance Trip Delay
Motor Insight
1–20 seconds (10) default
Voltage Faults Trip Mode
Motor Insight
0 = Trip on voltage fault
1 = Alarm-no-trip (inhibit start)—default
Jam Fault Trip Level
Motor Insight
150–400% of FLA (300%) default
Jam Fault Trip Delay
Motor Insight
1–60 seconds (5) default
Phase Loss Trip Delay
Motor Insight
1–20 seconds (10) default
Restart Delay
Motor Insight
0–500 seconds (10) default
Motor Fault Reset Delay
Motor Insight
2–500 minutes (8) default
Motor Faults—Number of Restarts
Motor Insight
0 = Manual, 1–4, 5 = Auto reset mode
Load Faults Reset Delay
Motor Insight
2–500 minutes (20) default
Load Faults—Number of Restarts
Motor Insight
0 = Manual, 1–4, 5 = Auto reset mode
Enable Load Faults Reset Delay Auto
Calculator
Motor Insight
0 = Reset Delay Auto Calc Off
1 = Reset Delay Auto Calc On
Run Transition % of FLA
Motor Insight
25–125%
Run Transition Time
Motor Insight
1–180 seconds
Phase Order
Motor Insight
0x0000 = Phase Order Trip Disabled
0x0001 = ACB Phase Order
0x0002 = ABC Phase Order
MI ComLoss Timeout
Motor Insight
0 = 65000 (msec)
MI ComLoss Behavior
Motor Insight
0x0001 = Fault (Fail Safe) Relay Off
0x0002 = Hold Last State
Enable MI AuxRly GND Trip Indication
Motor Insight
1 = Indication Enabled; 0 = No Indication (CP models only)
Enable MI AuxRly V Unbal Indication
Motor Insight
1 = Indication Enabled; 0 = No Indication (CP models only)
Enable MI AuxRly I Unbal Indication
Motor Insight
1 = Indication Enabled; 0 = No Indication (CP models only)
Enable MI AuxRly Under I Indication
Motor Insight
1 = Indication Enabled; 0 = No Indication (CP models only)
Table 17. C441 Motor Insight Configuration File, continued
Parameter Name
Location
Notes