Ratings
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
3
Ratings
The following ratings apply to the C441Q and C441S.
Table 3. Environmental Ratings of the Module
Table 4. Approvals and Certifications
Table 5. Input Power Supply Requirements
The following ratings apply to the C441QS and C441SS.
Table 6. Environmental Ratings of the Module
Table 7. EMC Requirement
Table 8. Input Power Supply Requirements
Description
Rating
Transportation
and Storage
Temperature
–40 °C to +85 °C (–40 °F to +185 °F)
Humidity
5–95% noncondensing
Operating
Temperature
–20 °C to +50 °C (–4 °F to +122 °F)
Humidity
5–95% noncondensing
Altitude
Above 2000 m (6600 ft), consult factory
Shock IEC
60068-2-27
15 G any direction for 11 milliseconds
Vibration IEC
60068-206
5–150 Hz, 5 G, 0.7 mm maximum
peak-to-peak
Pollution Degree
3
Electrical/EMC
Rating
ESD Immunity (IEC61000-4-2)
±8 kV Air, ±4 kV contact
Radiated Immunity (IEC61000-4-3) 10 V/m 80–1000 MHz, 80% amplitude
modulation @ 1 kHz
Fast Transient (IEC61000-4-4)
±2 kV using direct method
Surge (IEC61000-4-5)
±2 kV line-to-ground
RF Conducted (IEC61000-4-6)
10 V, 0.15–80 MHz
Ingress Protection Code
IP20
Radiated and Conducted Emissions EN55011 Class A
Agency Certifications
UL
®
508
cUL
®
(CSA® C22.2 No. 14)
CE (Low Voltage Directive)
Description
Requirement
Voltage Range
18–30 Vdc
Current Draw (Maximum)
30 mA
Description
Rating
Transportation
and Storage
Temperature
–40 °C to +80 °C (–40 °F to +176 °F)
Humidity
5–95% noncondensing
Operating
Temperature
–40 °C to +55 °C (–40 °F to +131 °F)
Humidity
5–95% noncondensing
Altitude
Above 2000 m (6600 ft), consult factory
Shock IEC
60068-2-27
15 G any direction for 11 milliseconds
Vibration IEC
60068-206
10–150 Hz, 3 G, 0.3 mm maximum
peak-to-peak
Pollution Degree
Pollution III
Polar Draw
<30 mA Steady State from 24 Vdc
Dielectric
withstand
Equipment rating volts more than 50 V,
potential volts AC 1000+2*V (max marked
voltage)
Item
Rating
Agency Certifications
cULus by UL to UL 508, CSA C22.2 No. 14
CE (Low Voltage Directive, EMC Directive)
C-TICK
Radiated and Conducted
Emissions
EN 55011 Class A
Electrical/EMC
ESD Immunity (IEC61000-4-2)
±8 kV Air, ±4 kV contact
Radiated Immunity (IEC61000-4-3) 10 V/m 80–1000 MHz,
80% amplitude modulation at 1 kHz
Fast Transient (IEC61000-4-4)
±2 kV supply and IO
±1 kV communications
Surge (IEC61000-4-5)
±2 kV Line to PE and ±1 kV Line-to-Line
RF Conducted (IEC61000-4-6)
10 V, 0.15–100 MHz
Magnetic Field (IEC61000-4-8)
DNA
Voltage Dips (IEC61000-4-11)
DNA
Protection Degree (IEC60947-1)
IP20
Electrical/EMC
Rating
Voltage Range
18–30 Vdc
Current Draw (Maximum)
30 mA