EC590
Function parameters description
EC590
Function parameters description
-
101
-
-
102
-
Function Code
Parameter Name
Default
A2-27
Encoder pulses per revolution
Setting Range
1024
1 to 65535
A2-28
Encoder type
0
0 to 2
A2-29
Speed feedback PG selection
0 to 2
A2-30
A/B phase sequence of ABZ incremental
encoder
0 to 1
A2-31
Encoder installation angle
0.0 to 359.9
A2-34
Number of pole pairs of resolver
1 to 65535
A2-37
Auto-tuning selection
0 to 3
0
0
0.0
1
0
5.8.4 User Programmable Card
1.Set whether user programmable card is valid.
Function Code
Parameter Name
Default
A7-00
User programmable function
selection
Setting Range
0
0: Disabled
1: Enabled
2. Set AI3 and AO2 function on user programmable card.
Function Code
Parameter Name
Default
A7-02
User programmable card A1
/
A0
function selection
Setting Range
0
0: Keyboard
potentiometer
(voltage input), AO2 (voltage output)
1: Keyboard
potentiometer
(voltage input), AO2 (current output)
2: Keyboard
potentiometer
(current input), AO2 (voltage output)
A7-02
User programmable card A1
/
A0
function selection
0
3: Keyboard
potentiometer
(current input), AO2 (current output)
4: Keyboard
potentiometer
(PTC input), AO2 (voltage output)
5: Keyboard
potentiometer
(PTC input), AO2 (current output)
6: Keyboard
potentiometer
(PT100 input), AO2 (voltage output)
7: Keyboard
potentiometer
(PT100 input), AO2 (current output)
3. Set the AC drive output signals
When A7-00 = 1 (user programmable card is enabled), you can set control source of output ter-
minals (FMR, relay, Y1, FMP and AO1) of the AC drive in A7-01.
When an output terminal is controlled by PLC program, output of terminal is determined by set-
ting of corresponding function parameter A7-03/A7-04/A7-05.
You can implement control of output terminal via PLC program by modifying A7-03/A7-04/
A7-05.
Function Code
Parameter Name
Default
A7-01
Control board output terminal
control mode selection
Setting Range
0
0
:
AC drive control
1:User programmable card control
BIT0
:
Y4R (Y4 used as digital output
)
BIT1
:
Relay (T/A-T/B-TC)
BIT2
:
Y1
BIT3
:
Y4P (Y4 used as pulse
control)
BIT4
:
AO1
A7-03
PLC program controls the FMP
output
0.0% to 100.0%
A7-04
PLC program controls the AO1
output
0.0% to 100.0%
A7-05
Selection of PLC program
controlling digital output
Binary
setting
BIT0:Y4R
BIT1
:
Relay 1
BIT2
:
Y
0.0%
0.0%
000
The base value of A7-03 is F5-09 (Max. FMP output frequency). The base value of A7-04 is 10 V
(voltage output) or 20 mA (current output).