3.10 AC drive control terminal connections
Analog input terminals (FS, FV, FI, FC)
■
The connection with analog signal is especially easy to be influenced
by the interference of external noise, thus the wire should be as short as
possible (less than 20m), and shielding wire should be used. The outer wire
mesh of the shielding wire should be basically grounded, but if the inducing
noise is very loud, it is better to connect it to the FC terminal.
■
For the need of using contact in this circuit, the double-fork contact
which can process weak signals should be used. Besides, the terminal FC should
not adopt contact control.
FV/FI
FC
C
Go through in-phase and encirle 3 loops or above
Ferrite magnetic ring
Input terminals of contact (S1~S8)
Output terminals of transistor(Y3, Y4 )
Input terminals of contact (S1~S8)
Output terminals of transistor (Y3,Y4)
■
While controlling the input of contacts, in order to prevent bad con-
tact, the contacts that have high reliability for the contact with weak sig-
nals should be used.
■
The polarity of the external power supply should be correctly connected.
■
While connecting the control relay, the surge absorber should be conne-
cted with the two ends of field coil. Please ensure that the polarity is corr-
ectly connected.
■
While connecting with the external analog signal follower, sometimes
the interference caused by the analog signal follower or the AC drive will
lead to misoperation, in such conditions, the capacitor and the magnetic core
of ferrite may be conncted to the external analog follower, as shown below:
Others
■
It's best to use the shielding wires as control wires, the isolation
network divested segment before the terminals should not be exposed.
■
The wires of control terminals should keep away from the wires of the
main loop, or misoperation may be caused due to noise interference. If an
intersection is needed, make them intersect with a right angle.
■
Generally the control wires don't have good insulation. If the insula-
tion layer is broken due to some reason, high voltage may enter the control
circuit (control panel), leading to circuit damage, equipment accidents or
personal Danger
.
■
The control wires in the AC drive should be fixed properly to prevent
them from the direct contact with the charge-carrying part of the main circuit
(e.g. the terminal strips of the main circuit).
EC590
EC590
Mechanical and electrical installation
Mechanical and electrical installation
-
23
-
-
24
-
Type
Power
supply
Analog
input
Terminal
Function Description
P10V power supply for external unit, maximum output
current: 10mA
Generally, it provides power supply to external potentiometer
with resistance range of 1kΩ.
~
5kΩ.
P24V power supply to external unit, generally, it
provides power supply to S/Y terminals and external sensors.
Maximum output current: 100mA
Connect to +24V by default when S1
~
S6 need to be driven by
external signal, PLC needs to be connected to external power
supply and be disconnected from +24V power supply terminal.
1. Input voltage range: DC 0V
~
10V
2. Impedance: 22kΩ
1. Input range: DC 0V
~
10V/4mA–20mA
,
decided by selection
of F4-40.
2. Impedance: 22kΩ(voltage input),500Ω(current input)
10V-GND
24V-COM
PLC
AI1-GND
AI2-GND
Name
E10V
power supply
E24V
power supply
Input terminal
of external
power supply
Analog input
termianl 1
Analog input
termianl 2
Digital
input
1. Optocoupler coupling isolation, compatible with dual
polarity input
2. Impedance: 2.4kΩ
3. Voltage range for level input: 9V-30V
4. S5 can be used for high-speed pulse input.
Maximum input frequency: 50kHz
S1-COM
Digital input 1
S
3
-COM
S
2
-COM
S
4
-COM
S
5
-COM
S
6
-COM
Digital input 3
Digital input 2
Digital input 4
Digital input 5
Digital input 6
Voltage or current output of A01 is decided by F5-23.
Voltage or current output of A02 is decided by F5-24.
Output voltage range: 0V
~
10V
Output current range: 0mA
~
20mA
AO1-GND
Analog output
terminal 1
Analog
output
AO2-GND
Analog output
terminal 2
Digital
output
Commun-
ication
Contact driving capacity:
250Vac, 3A, COSØ=0.4.
30Vdc, 1A
Y3-YC
Y4-YC
Y1A/Y1B/
Y1C
DA,DB
Relay digital
output 1
Trnsistor
digital
output 3
Trnsistor
digital
output 4/
High-speed
pulse output
1.Optocoupler coupling isolation, dual polarity open
collector output:
2.Output voltage range: 0
~
24 V
3.Output current range: 0
~
50 mA
4.Y4 is limited by F5-00 “HY function enable”. As high-
speed pulse output, the maximum
frequency is 1000 kHz. When
output as open collector, the specification is the same as Y3.
5.It’s disconnected by default at the factory. If you need
to connect, you can short-circuit YC and COM by yourself.
1. Standard RS485 communication interface;
RS485 interface