129
-
-
130
-
Parameter adress
Description
100FH
Load speed
-
-
101FH
1020H
Main frequency reference display
Auxiliary frequency reference display
Parameter adress
Description
●
Communication setting value indicates percentage: 10000 corresponds to 100.00%,
and -10000 corresponds to -100.00%.
●
With regard to frequency, communication reference is a percentage of F0-10 (max.
frequency).
●
With regard to torque, communication reference is a percentage of F2-10 and A2-48
(corresponding to motor 1 and motor 2, respectively).
Note
Command Word Address
Command Word Function
2000H
0001: Forward run
0002: Reverse run
0003: Forward jog
0004: Reverse jog
0005: Coast to stop
0006: Decelerate to stop
0007: Fault reset
Control command input to AC drive (write-only):
Read AC drive state (read-only):
Command Word Address
Command Word Function
3000H
0001: Forward run
0002: Reverse run
0003: Stop
Parameter lock password verification: if the actual password value is returned, it means that the
password verification is passed.(If there is no password, that is the password is 0, the check returns
0000H)
Password Address
Password Content
1F00H
*****
Y terminal control (write-only)
Command Address
Command Content
2001H
BIT0: Y1 control
BIT1: Y2 control
BIT2: RELAY1 control
BIT3: RELAY2 control
BIT4: Y4R control
BIT5: VY1
BIT6: VY2
BIT7: VY3
BIT8: VY4
BIT9: VY5
AO1 control (write-only)
Command Address
Command Content
2002H
0 to 7FFF indicates 0% to 100%.
AO2 control (write-only)
Command Address
Command Content
2003H
0 to 7FFF indicates 0% to 100%.
Pulse output control (write-only)
Command Address
Command Content
2004H
0 to 7FFF indicates 0% to 100%.
EC590
Function parameters description
EC590
Function parameters description