80
/
96
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-7-1-1-1
Drinking water filling
Disabled
Disabled
Everybody
Service
-
Enabled
2-7-1-2
Tank level
-
-
-
-
-
2-7-1-2-4
Absolute height at 0 %
0 … absolute height at 100 %
Position of sensor
above tank-bottom
Everybody
Service
-
2-7-1-2-5
Absolute height at 100 %
Absolute height at 0 % … 2000 cm
200 cm
Everybody
Service
-
2-7-1-2-6
Position of sensor above tank
bottom
0 … level at 20 mA
20 cm
Everybody
Service
-
2-7-1-2-7
Low-water level
0 … low-water reset level
0,1
Everybody
Service
-
2-7-1-2-8
Low-water reset level
Low-water level … critical water level
0,15
Everybody
Service
-
2-7-1-2-9
Critical water level
Low-water level … high-water level
0,3
Everybody
Service
-
2-7-1-2-10
Level for reset critical water level
Critical water level … high-water level
0,35
Everybody
Service
-
2-7-1-2-11
Start tank filling level
Low level … stop tank filling level
0,5
Everybody
Service
-
2-7-1-2-12
Additional start tank filling level
Low level … start tank filling level
0,4
Everybody
Service
-
2-7-1-2-13
Additional stop tank filling level
Start tank filling level … stop tank filling level 0,9
Everybody
Service
-
2-7-1-2-14
Stop tank filling level
Start tank filling level … high-water level
1
Everybody
Service
-
2-7-1-2-15
Level for reset high-water level
Stop tank filling level … high-water level
1,2
Everybody
Service
-
2-7-1-2-16
High-water level
Stop tank filling level … according to sensor
type or level at 20 mA
1,25
Everybody
Service
-
2-7-1-3
Tank filling
-
-
-
-
-
2-7-1-3-1
Inlet valve type
Tank filling on/off valve
Tank-filling on/off
valve
Everybody
Service
-
Tank filling proportional valve
2-7-1-3-2
Minimum opening angle of valve
0 … 100 %
0,1
Everybody
Service
-
2-7-1-3-3
Step width for valve actuation
0 … 100 %
0,1
Everybody
Service
-
2-7-1-4
Additional tank filling
-
-
-
-
-
2-7-1-4-1
Additional tank filling
Disabled
Disabled
Everybody
Service
-
Enabled
2-7-1-4-2
Inlet valve type
Tank filling additional solenoid valve
Additional tank-filling
solenoid valve
Everybody
Service
-
Tank filling proportional valve
2-7-1-4-3
Minimum opening angle of valve
0 … 100 %
0,1
Everybody
Service
-
2-7-1-4-4
Step width for valve actuation
0 … 100 %
0,1
Everybody
Service
-
2-7-1-5
Drinking water protection
-
-
-
-
-
2-7-1-5-1
Drinking water protection
Disabled
Enabled
Everybody
Service
-
Enabled