75
/
96
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-4-2-6
Ramp down time
0 … 60 s
0
Everybody
Service
-
2-4-3
Changeover from jockey pump to
base load pumps
-
-
Everybody
Service
-
2-4-3-1
Over-/undersupply
Oversupply
Oversupply
Everybody
Service
-
Undersupply
2-4-3-2
Time of over-/undersupply
0 … 60 s
10 s
Everybody
Service
-
2-4-4
Check run
-
-
-
-
-
2-4-4-1
Check run
Disabled
Enabled
Everybody
Service
-
Enabled
2-4-4-2
Function
Idle time dependent
Time-dependable
Everybody
Service
-
Time-of-day configured
Triggered check run
2-4-4-3
Duration
0 … 600 s
10 s
Everybody
Service
-
2-4-4-4
Standstill time
0: 00: 00: 00 … 7: 00: 00: 00 d: hh: mm: ss
24 h
Everybody
Service
-
2-4-4-5
Time stamp for activation (hours)
Day of week, time
Mo, 12: 00: 00
Everybody
Service
-
2-4-4-6
Time stamp for execution (minutes)
Day of week, time
Mo, 12: 00: 00
Everybody
Service
-
2-4-5
Short pressure deviations
-
-
-
-
-
2-4-5-2
Delay time for pump start
0 … 60 s
0
Everybody
Service
-
2-4-5-3
Delay time for pump stop
0 … 60 s
0
Everybody
Service
-
2-4-6
No-flow detection
-
-
Everybody
Service
-
2-4-6-1
Pump speed for activation
0 % … 100 %
1
Everybody
Service
-
2-4-6-2
Time within bandwidth
0 … 600 s
15 s
Everybody
Service
-
2-4-6-3
Step interval
0 … 600 s
15 s
Everybody
Service
-
2-4-6-4
Step height of speed
1 % … 50 %
0,03
Everybody
Service
-
2-4-6-5
Bandwidth
0 … bandwidth
0.05 bar
Everybody
Service
-
2-4-6-6
Speed for stopping last pump
0 % … 100 %
0
Everybody
Service
-
2-4-7
Dynamic pressure setpoint
compensation
-
-
-
-
-
2-4-7-1
Dynamic pressure setpoint
compensation
Disabled
Disabled
Everybody
Service
-
Enabled
2-4-7-2
Maximum discharge-side pressure
deviation
-10 bar … 10 bar
0
Everybody
Service
-
2-4-8
Motor circuit breaker
-
-
-
-
-
2-4-8-1
Trigger active high/low
Active high
1: Active low
Everybody
Service
-