Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-3-3-1
1-3-3-2
1-3-3-3
1-3-3-4
1-3-3-5
1-3-3-6
1-3-3-7
1-3-3-8
1-3-3-9
1-3-3-10
1-3-3-16
1-3-3-17
1-3-3-18
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 16 (extension board)
Input 17 (extension board)
Input 18 (extension board)
Manual-mode at M-0-A-switch rainwater
pump 2
None
Everybody
Service
-
Automatic-mode at M-0-A-switch rainwater
pump 1
Automatic-mode at M-0-A-switch rainwater
pump 2
Float switch in rainwater tank
External On/Off
Fire alarm
Acknowledge all
Alternative setpoint
Triggered check run
Emergency power operation
Forced flushing
Module water quality sensor/monitoring
Membrane rupture detection
Leakage-detection by external device
Failure supply-valve
Failure additional supply-valve
Redundant system
1-3-4
Digital output
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
-