Communication solutions for power utilities
UNIVERSAL TELEPROTECTION TPU-1
INSTALLATION AND COMMISSIONING MANUAL Web version TPU-1R - Rev. 5.9 (May 2018)
48/69
7.2
STORAGE
Check that the boxes received do not have bumps or dents and that the packaging is not
damaged. In the case of cardboard boxes check that the seal is not broken in any side.
The user must immediately notify ZIV of any anomaly about the original
packaging.
Before storing the box check that the material supplied corresponds to the requested. To do
this, check the supplied material in the delivery note enclosed in the bag labelled
“
Contains
Documentation. Packing List
”.
The user must immediately notify ZIV of any anomaly about the material received
and, if applicable, return all material to ZIV in the original package.
The TPU-1 terminals should be stored in its own packaging until installation.
Storage must be done in premises protected from the weather, Class C according
to EN 60870-2-2 standard.
The temperature range should be between -20°C and +70°C.
The boxes should be stacked in a flat position. A maximum of twelve boxes, one
above the other can be stacked.
In protected installations (Class C), neither the temperature nor the humidity are controlled.
The equipment are protected from direct sunlight, rain and other precipitation and wind.
It is convenient to unpack the equipment as needed.
In the process of unpacking the cardboard boxes, it is recommended to use a
utility knife or another sharp object to unseal the adhesive band in the sides of the
box. Once unsealed on the sides, it is advisable to fully pull the band without using
a utility knife or another sharp tool.