Single-Ended I/O Modules
UltraSCSI RAID Enclosure 5–13
Table 5–6 Installing Three Enclosure Subsystem Cables
1. Shut down the array controller (see Table 5–5).
Use a screwdriver to loosen the two, spring-loaded mounting screws
on the I/O module.
2. Grasp the module by the cable support bracket and pull it directly to
the rear and remove it from the enclosure shroud.
CXO5816A
3. Repeat Steps 1 and 2 for all the I/O modules.
4. On the first (master) I/O module, align the Cable A connector with
the left connector.
CXO5854A
Cable A
Gently insert the cable connector into module connector. Tighten
both cable connector thumb screws to fully seat the connector.
Install a wire tie through the holes on the cable support bracket and
around the cable. Tighten the wire tie.
5. Align the module with the Port 1 backplane connector in the master
enclosure shroud. Gently insert the module and fully seat it. Use a
screwdriver to tighten the spring-loaded mounting screws.