INSTALLATION
4–37
4.7 HA320-AA/AB REMOTE STATUS PANEL
The Remote Status Panel allows monitoring of UPS system parameters and provides a
display of alarms and diagnostic messages from up to 91.4 m (300 ft) away from the UPS
cabinet.
A 7-conductor shielded cable assembly is provided with the Remote Status Panel and
must be connected to TB3 in the UPS cabinet.
Use the following procedure to connect the power and control wires from the Remote
Status Panel to TB3 in the UPS cabinet:
1. Route the shielded cable into the cable entry area of the UPS cabinet.
2. From the shielded cable jacket containing three 16 AWG wires, connect the green
wire to TB3-1 in the UPS cabinet.
3. From the shielded cable jacket containing three 16 AWG wires, connect the white
wire to TB3-3 in the UPS cabinet.
4. From the shielded cable jacket containing three 16 AWG wires, connect the black
wire to TB3-2 in the UPS cabinet.
5. From the shielded cable jacket containing four (two twisted pair) 18 AWG wires,
connect the black #1 wire to TB3-4 in the UPS cabinet.
6. From the shielded cable jacket containing four (two twisted pair) 18 AWG wires,
connect the red #1 wire to TB3-5 in the UPS cabinet.
7. From the shielded cable jacket containing four (two twisted pair) 18 AWG wires,
connect the black #2 wire to TB3-6 in the UPS cabinet.
8. From the shielded cable jacket containing four (two twisted pair) 18 AWG wires,
connect the red #2 wire to TB3-7 in the UPS cabinet.