4–24
INSTALLATION
4.5 HA33D/F UPS CSA CABINET
The HA33D/F UPS CSA Cabinet is designed to attach to the right side of the UPS cabinet
(Figure 2–6).
Place the UPS cabinet in its final position. Remove the right side panel and the cover
plate for the side cable entry area.
NOTE
The side panels are not provided with the UPS CSA Cabinet. Remove the right
side panel from the UPS cabinet and attach it to the right side of the UPS CSA
Cabinet after installation.
Place the HA33D/F UPS CSA Cabinet on the right side of the HA32A UPS cabinet. The
two cabinets must be attached together; three holes are provided for this purpose. Two
holes are accessible from the front, and the third can be reached from the top-rear of the
enclosure (Figure 4–15). The bolts are provided with the HA33D/F UPS CSA Cabinet.
419 mm
(16.54 in)
613.92 mm
(24.17 in)
229 mm
(9.10 in)
TOP
LEFT SIDE VIEW OF
UPS CSA CABINET
FRONT
BACK
MOUNTING
HOLES
(3 PLACES)
1401.58 mm
(56.18 in)
CABLE
FEED
AREA
M K V - A 2 2 3 9 - 9 1
Figure 4–15
UPS CSA Cabinet Mounting Holes