4–18
INSTALLATION
Table 4–4 (Cont.)
HA32C/D/E UPS Auxiliary Cabinet Electrical Specifications
Model
Number
Output
Rating
(kVA)
Input
Voltage
(Vac)
Input
Current
(Amps)
Output
Voltage
(Vac)
Output
Current
(Amps)
Input CB
Rating
(Amps)
HA32D-DH
20
220
59
220
59
90
HA32D-EH
20
600
24
208
62
40
HA32D-AK
40
208
122
208
122
175
HA32D-BK
40
480
53
208
122
90
HA32D-CK
40
480
53
480
53
90
HA32D-DK
40
220
115
220
115
175
HA32D-EK
40
600
43
208
122
60
HA32D-AM
60
208
181
208
181
250
HA32D-BM
60
480
79
208
181
100
HA32D-CM
60
480
79
480
79
100
HA32D-DM
60
220
171
220
171
250
HA32D-EM
60
600
63
208
181
80
HA32D-AN
80
208
238
208
238
350
HA32D-BN
80
480
103
208
238
150
HA32D-CN
80
480
108
480
103
150
HA32D-DN
80
220
225
220
225
350
HA32D-EN
80
600
93
208
238
100
With Harmonic Current Filter Only
HA32E-PH
20
NA
NA
NA
NA
NA
HA32E-PK
40
NA
NA
NA
NA
NA
HA32E-PM
60
NA
NA
NA
NA
NA
HA32E-PN
80
NA
NA
NA
NA
NA
NOTES:
1. NA = Not Applicable
2. The Input Harmonic Current Filter option is not voltage dependent. It does not increase the input or output
current.
3. The UPS Auxiliary Cabinet models with an Input Isolation Transformer (HA32C and HA32D) contain an
input circuit breaker (CB1).
Field wiring connections for the isolation transformer are made on the line side of the
circuit breaker CB1. To gain access to this area, the door of the UPS Auxiliary Cabinet
must be unlocked and opened, and the upper inside cover panel must be removed.