INSTALLATION
4–11
TB1
1
12
POS.
NEG. GND.
MKV-A2210-91
UPS BATTERY CABINET
CONTROL WIRING
TB1-1
QF1 24 Vdc UV RELEASE
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
NOT USED
N.O.
COMM.
NOT USED
TB1-7
TB1-8
DC GROUND FAULT
DETECTOR
TB1-9
TB1-10
SMOKE DETECTOR
CONTACTS
TB1-11 +24 Vdc
TB1-12 COMM.
SMOKE DETECTOR
POWER SUPPLY
QF1 AUXILIARY
CONTACT
Figure 4–4
UPS Battery Cabinet Power and Control Wiring Connections
4.3.3 Two UPS Battery Cabinets/HA32A UPS Installation
When two UPS Battery Cabinets are required to meet the specified backup or protection
time, each should be installed according to the directions in Section 4.3.2. Except for
a common chassis ground connection, no connections should be made between the UPS
Battery Cabinets.
4.3.4 Power Cable Connections
The power cable connections should be made after selecting the appropriate size wire
that satisfies the maximum permissible cable voltage drop requirements specified in
Section 4.3.1. Make sure that the correct polarities are observed when making all dc
connections. Positive (+) to positive and negative (-) to negative.
Power cable connections and the chassis ground connection are made on the inside rear,
top right portion of the UPS Battery Cabinet (Figure 4–4).
See Figure 4–1 for the UPS Battery Cabinet power cable connections in the UPS cabinet.
See Figure 4–3 for the chassis ground connection in the UPS cabinet.