4.6 HA32J/K UPS DISTRIBUTION CABINET
The HA32J/K UPS Distribution Cabinet is designed to attach to the right side of the
HA32A UPS cabinet (Figure 2–7), or to the right side of the HA32C/D/E UPS Auxiliary
Cabinet or HA33D/F UPS CSA Cabinet (Figure 2–8), if one or both of these options have
been purchased.
NOTE
The side panels are not provided with the UPS Distribution Cabinet. The right
side panel from the UPS cabinet, the UPS Auxiliary Cabinet, or the UPS CSA
Cabinet must be removed and attached to the right side of the UPS Distribution
Cabinet after installation.
Place the HA32A UPS cabinet in its final position. Remove the right side panel and the
cover plate for the side cable entry area.
If the HA32C/D/E UPS Auxiliary Cabinet or the HA33D/F UPS CSA Cabinet option is
purchased, install them on the right side of the HA32A UPS cabinet.
All cabinets must be attached together; three holes are provided for this purpose
(Figure 4–19). The bolts are provided with the HA32J/K UPS Distribution Cabinet.
419 mm
(16.54 in)
229 mm
(9.10 in)
TOP
LEFT SIDE VIEW OF
UPS DISTRIBUTION CABINET
FRONT
BACK
CABLE
FEED
AREA
M K V - A 2 2 1 8 - 9 1
MOUNTING
HOLES
(3 PLACES)
Figure 4–19
UPS Distribution Cabinet Mounting Holes