4–6
INSTALLATION
4.2.5.1 Battery Cabinet Circuit Breaker (QF1) Control Wiring
The UPS Battery Cabinet circuit breaker requires four (4) wires (TB1-3 and TB1-6 are
not used).
Use the following procedure to connect the Battery Cabinet circuit breaker control wires
to the UPS cabinet control wiring interface.
1. Connect a control wire from TB1-1 in the UPS Battery Cabinet to TB1-1 in the UPS
cabinet.
2. Connect a control wire from TB1-2 in the UPS Battery Cabinet to TB1-2 in the UPS
cabinet.
3. Connect a control wire from TB1-4 in the UPS Battery Cabinet to TB1-4 in the UPS
cabinet.
4. Connect a control wire from TB1-5 in the UPS Battery Cabinet to TB1-5 in the UPS
cabinet.
4.2.5.2 DC Ground Fault Detector Control Wiring
The DC Ground Fault Detector requires two (2) control wires if it is or will be installed
in the UPS Battery Cabinet.
Use the following procedure to connect the DC Ground Fault Detector control wires
between the UPS Battery Cabinet and the UPS cabinet control wiring interface.
1. Connect a control wire from TB1-7 in the UPS Battery Cabinet to TB1-7 in the UPS
cabinet.
2. Connect a control wire from TB1-8 in the UPS Battery Cabinet to TB1-8 in the UPS
cabinet.
4.2.5.3 Smoke Detector Control Wiring
The Smoke Detector requires four (4) control wires if it is or will be installed in the UPS
Battery Cabinet.
Use the following procedure to connect the Smoke Detector control wires between the
UPS Battery Cabinet and the UPS cabinet control wiring interface.
1. Connect a control wire from TB1-9 in the UPS Battery Cabinet to TB1-9 in the UPS
cabinet.
2. Connect a control wire from TB1-10 in the UPS Battery Cabinet to TB1-10 in the
UPS cabinet.
3. Connect a control wire from TB1-11 in the UPS Battery Cabinet to TB1-11 in the
UPS cabinet.
4. Connect a control wire from TB1-12 in the UPS Battery Cabinet to TB1-12 in the
UPS cabinet.