4.8 HA320-A3 REMOTE ALARM PANEL
The Remote Alarm Panel allows the UPS system status to be monitored from a remote
location. The unit is mounted on a wall using the four mounting holes located on the
back of the unit.
For the installation of the Remote Alarm Panel option, six (6) control wires and two (2)
power wires must be provided and installed by the customer’s electrician.
Use the following procedure to connect the six control wires from TB3 in the Remote
Alarm Panel to TB2 and TB3 in the UPS cabinet, and to connect the two power wires
from a 120 Vac source to TB3 in the Remote Alarm Panel:
1. Connect a control wire from TB3-1 in the Remote Alarm Panel to TB3-12 in the UPS
cabinet.
2. Connect a control wire from TB3-2 in the Remote Alarm Panel to TB2-1 in the UPS
cabinet.
3. Connect a control wire from TB3-3 in the Remote Alarm Panel to TB3-9 in the UPS
cabinet.
4. Connect a control wire from TB3-4 in the Remote Alarm Panel to TB2-4 in the UPS
cabinet.
5. Connect a control wire from TB3-9 in the Remote Alarm Panel to TB2-2 in the UPS
cabinet.
6. Connect a control wire from TB3-11 in the Remote Alarm Panel to TB3-11 in the UPS
cabinet.
7. Connect the two power wires from a 120 Vac source to TB3-14 and TB3-15 in the
Remote Alarm Panel.