SPECIFICATIONS
B–5
Table B–2
HA32A Currents
HA32A-xH
HA32A-xK
HA32A-xM
HA32A-xN
Output Power Rating
kVA/kW
20/16
40/32
60/48
80/64
Unit Nominal AC Input Current (Amperes) @ Nominal Input Voltage
208 Vac
61.5
121.5
180.4
237.7
220 Vac
58.2
114.9
170.5
224.8
480 Vac
29.3
52.7
78.2
103.0
Unit AC Output and Bypass AC Input Current (Amperes) @ Nominal Voltage (Note 1)
Full Load Continuous
208Y/120
55.5
111.0
166.5
222.1
220Y/127
52.5
105.0
157.5
209.9
480Y/277
24.1
48.1
72.2
96.2
125% Overload for 10 Minutes
208Y/120
69.4
138.8
208.2
277.6
220Y/127
65.6
131.2
196.8
262.4
480Y/277
30.1
60.1
90.2
120.3
150% Overload for 1 Minute
208Y/120
83.3
166.5
249.8
333.1
220Y/127
78.7
157.5
236.2
314.9
480Y/277
36.1
72.2
108.3
144.3
Maximum Battery Current (Note 2)
Amperes
54.6
109.2
163.9
218.5
NOTES:
1. As a minimum, bypass ac input (MAINS2) power should match the UPS output rating. The bypass ac input
should have a continuous rating of 125% of the UPS output power rating to supply fault-clearing current.
2. Battery wiring should be sized to keep the total cable voltage drop to less than 0.5 Vdc at the current
shown.
Summary of Contents for HA3000
Page 7: ...Contents vii B 10 UPS Distribution Cabinet Specifications B 11...
Page 8: ......
Page 82: ......
Page 94: ......