Rack Installation Instructions

For 1500 VA, 2200 VA, and 3000 VA uninterruptible power
supplies and 2200 VA and 3000 VA extended battery modules

Use the instructions in this document to install the 1500 VA, 2200 VA, and 3000 VA uninterruptible power
supplies and 2200 VA and 3000 VA extended battery modules in a rack cabinet.

Review the documentation that comes with your rack cabinet for safety and cabling information.

When you install the uninterruptible power supply or extended battery module in a rack cabinet, observe
the following precautions:

v

The extended battery module and uninterruptible power supply internal battery and chassis are heavy.
Make sure that you have the minimum number of persons required to lift the components. See Table 1
on page 6 and Table 2 on page 7.

v

Make sure that the room air temperature is below 35°C (95°F).

v

Do not block any air vents; usually 15 cm (6 in.) of air space provides proper airflow.

v

Plan the device installation starting from the bottom of the rack cabinet.

v

Install the heaviest device in the bottom of the rack cabinet.

v

Do not extend more than one device out of the rack cabinet at the same time.

v

Connect all power cords to properly wired and grounded electrical outlets.

v

Do not overload the power outlet when you install multiple devices in the rack cabinet.

You will need a Phillips screwdriver to install the uninterruptible power supply or extended battery
module in a rack cabinet.

Note:

The illustrations in this document might differ slightly from your hardware.

The following parts come with the rack mounting kit:

v

One right adjustable rail

v

One left adjustable rail

v

Four adapter plates with adhesive (for round hole racks)

v

Sixteen M5 x 16 mm Phillips screws

Note:

Removing the rack doors and side panels might make installation easier. See the rack cabinet
documentation for more information.

Summary of Contents for 1500VA

Page 1: ...below 35 C 95 F v Do not block any air vents usually 15 cm 6 in of air space provides proper airflow v Plan the device installation starting from the bottom of the rack cabinet v Install the heaviest...

Page 2: ...mage v Disconnect the attached power cords telecommunications systems networks and modems before you open the device covers unless instructed otherwise in the installation and configuration procedures...

Page 3: ...battery module in the rack cabinet complete the following steps 1 For racks with round holes only Install one adapter plate on each of the ends of the right and left rails a Locate the four adapter pl...

Page 4: ...ible power supply or extended battery module 4 Secure each rail to the front of the rack with two M5 x 16 mm screws Make sure that the rails are on the inside of the rack cabinet mounting flanges and...

Page 5: ...upply remove the internal battery module a Loosen the thumbscrew on the metal battery cover 1 slide the cover to the right 2 and open the cover 3 b Using the plastic tabs pull the battery module parti...

Page 6: ...b One person 2200 VA internal battery module 16 3 kg 36 lb One person 3000 VA internal battery module 21 3 kg 47 lb Two persons d With two hands pull the battery module fully out of the bay and place...

Page 7: ...1 7 lb chassis only One person 5395 3AX 3000 VA 3U rack uninterruptible power supply 17 2 kg 37 9 lb chassis only One person 5395 3JX 3000 VA 3U rack uninterruptible power supply 17 9 kg 39 4 lb chass...

Page 8: ...terruptible power supply installation only To reinstall the battery module complete the following steps a Loosen the thumbscrew on the metal battery cover 1 slide the cover to the right 2 and open the...

Page 9: ...ttery module 8 kg 18 lb One person 2200 VA internal battery module 16 3 kg 36 lb One person 3000 VA internal battery module 21 3 kg 47 lb Two persons OK OK 10 0 6 m in 1500VA 208V 60h z UPS ON OK OK 1...

Page 10: ...the thumbscrew 3 12 Locate the bezel that comes with the uninterruptible power supply or extended battery module Press the two side latches toward each other align the bezel with the uninterruptible p...

Page 11: ...e power supply For more information about installing and operating the uninterruptible power supply and extended battery module see the Installation and Maintenance Guide that comes with the uninterru...

Page 12: ...usiness Machines Corporation in the United States other countries or both Printed in USA Copyright IBM Corporation 2010 2011 US Government Users Restricted Rights Use duplication or disclosure restric...

Reviews: