Configure MODBUS Gateway parameters
Digi TransPort User Guide
564
Enable MODBUS Gateway
Enables or disables MODBUS gateway instance.
Async Port
The local serial port number (asynchronous port) for the MODBUS serial interface.
Async Mode
The serial driver for RS232 or RS485 on supported hardware.
Duplex Mode
The duplex mode, which can be
half
or
full
. Use
full
for 4-wire installations; otherwise
half
is
required.
Operation mode
The operation mode to master or slave.
Idle Gap
When receiving an modbus response from a station when this idle gap (pause with no
reception of characters) is detected the message (currently received from the station) is at that
staged forwarded on as the complete response.
Fix slave address
The address of the slave is fixed at this value. An address conversion will occur if a message
that does not contain this address is received from the TCP master. If not used, the TCP
master must use the correct slave address.
Adjust slave address
The address of the slave is adjusted by this value. If left at
0
, the slave address is not adjusted
at all.