General data
Volume pulse input:
o
0,01…10000 L/Imp.
o
200 Hz max. at pulse duration > 3ms
Temperature sensor:
o
PT500/PT100 in 2/4 wire
o
There are no wired shortcut necessary
Ambient temperature: 5 … 55 °C
Application:
o
heating: 5 … 130°C (150°C)
o
cooling: 1 … 90°C
o
heating with cooling tariff: 1 … 105 °C
4.3
Power supply
External power supply
230 V AC module / 24 V AC module (Fig. C, item 2, page 10)
Terminals suitable for wires up to 2.5 mm²
Electrical isolation
Frequency 50 Hz
Power consumption 0.12 VA ±10 %
Soldered fuse (50mA)
The cable is to be fused at max. 6A and protected against manipulation.
4.4
Calculator interfaces
4.4.1 Communication modules
M-Bus
M-Bus module to EN 1434-3 standard
2-pole terminal strip with terminals marked “24” and “25”
Terminals suitable for a cable with 2 wires of 2.5 mm²
Electrical isolation
Polarity reversal protection
Maximum voltage: 50 V DC
Current drawn: one M-Bus load
Primary or secondary addressing
Baud rate 300 or 2400 bauds (automatic baud rate detection)
Protocol: M-Bus
max. reading interval
at battery supply A-Cell: every 3 minutes*
at battery supply D-Cell: each minutes*
at mains supply: unlimited
* If the calculator is reads
more, then the meter recognizes and doesn´t allow it. The display will show
then the error code E - 5. In addition, this error code will be shown in the header of the M- Bus
telegram (to frequent reading via M-Bus).
Fig. G
M-Bus module