Seite 23 von
71
Modbus RTU
Polarity independent: Connections 60 and 61
External power supply: 12-24 V AC/DC
Energy consumption: max. 150 mW
Connection 90 (not inverted, +)
Connection 91 (inverted, +)
Communications protocol: Modbus RTU
Channel EIA-485 (electrically isolated)
Flexible data format: Standard 9600 bits/s, 8N1, Modbus Slave ID-1
Fig. K
Modbus RTU Modul
LonWorks
Polarity independent: Connections 60 and 61
External power supply: 12-24 V AC/DC
Energy consumption: max. 150 mW
Polarity independent: Connections 96 (A) and 97 (B)
Channel TP/FT-10
Baud rate: 78: kbit/s
Data format: Differential Manchester encoding
electrically isolated
Fig. L
LonWorks module
Summary of Contents for SCYLAR INT 8
Page 19: ...Seite 19 von 71 4 Technical data 4 1 Dimensions Fig F Dimensions ...
Page 67: ...Seite 67 von 71 13 Declaration of conformity ...
Page 68: ...Seite 68 von 71 ...
Page 69: ...Seite 69 von 71 ...
Page 70: ...Seite 70 von 71 ...
Page 71: ...Seite 71 von 71 ...