01/2018
34 / 80
6159933780
Issue no: 09
CVIL II
7.7.3 - INPUT menu
Do not change SCY and DIR settings.
Inputs
Name
Factory
config.
Comments
Cycle 1 selection CYC1
X
Binary coding - weight 1, i.e. from 0 to 1.
Cycle 2 selection CYC2
X
Binary coding - weight 2, i.e. from 0 to 3.
Cycle 4 selection CYC4
X
Binary coding - weight 4, i.e. from 0 to 7.
Cycle 8 selection CYC8
X
Binary coding - weight 8, i.e. from 0 to 15.
Cycle 16 selection CYC16
Binary coding - weight 16, i.e. from 0 to 31.
Spindle validation SPVAL
X
Validates - or not - the tool start in both tightening directions if "Sp. val."
is enabled in the Station Menu.
Tightening
direction
validation
VPSTIG
Validates - or not - the tool start in the tightening direction if"Sp. val." is
enabled in the Station Menu.
Run reverse
direction
validation
VPSLOO
Validates - or not - the tool start in the run reverse direction if "SpV.rrv" is
enabled in the Station Menu.
Error
acknowledgement
ACKNOW
Validates again the tool operation after a reject report if the error
acknowledgement function in the Station Menu is enabled.
Start cycle
SCY
X
The cycle is run as long as the signal is at 1.
When the signal drops, the cycle stops and the report is sent to the PLC.
Tightening / Run
reverse
DIR
X
Validates the un-tightening direction as soon as the Start Cycle signal
appears, at the speed programmed in the Station Menu and with the
maximum current of the tool.
Reset
RESET
X
This signal resets the tightening reports and deletes the results
displayed.
External stop
EXSTOP
When the parameter is programmed on Yes in the programming screen
of the run down speed, final speed and run reverse phases, the system
stops the current phase on a pulse and switches to the next one.