Chapter 17 Introduction to BACnet
│CFP2000
17-7
3. Steps to setup the Parameters about BACnet in CFP2000
Related to BACnet function in CFP2000, We have to configure 2 parts of parameters
Part1. Setup parameters related to Communication at Pr_Group9.
Part2. Setup parameters related to System_Parameter at Pr_Group0.
Part1. Pr_Group9, Communication.
1-1. Set Pr.09-31 =1, BACnet is enabled, then the COM1_Port will be accessed by BACnet. When this
is set, the COM1_Port communication format will be changed to RTU 8, N, 1.
(Note: The HW Pins of COM1_Port are shared by RJ45 and RS-485. When BACnet is enabled,
BACnet will access the COM1_Port, that also means we can
NOT
have Modbus, PLC connections,
VFDSoft and VFD Explorer by COM1_Port).
1-2. Set Pr.09-50, Default = 10, BACnet’s MS/TP station number 0
–
127
1-3. Set Pr.09-51, Default = 38400, BACnet communication baud rate, 9600, 19200, 38400 or
76800 bps.
1-4. Set Pr.09-52 and Pr.09-53, the default setting of Device Object_Identifier is 0x000A (Pr.09-52=10,
Pr.09-53=00). Device Object_Identifier is the combination of Pr.09-52 and Pr.09-53, thus the
setting range can be 0
–
4194303.
For example, Pr.09-53=12(0x0C) and Pr.09-52 =3456(0x0D80), then the device Identifier’s value
=12*65536+3456 =789888(0x0C0D80).
1-5. Set Pr.09-55, Default =127, the highest allowable address for master nodes on the same MS/TP
network. CFP2000 base on this setting to know the Max search range.
1-6. Set Pr.09-56, setup the BACnet password. If setup is successful, the keypad will display 8888.
Part2. Pr_Group0, System Parameter.
2-1. Set Pr.00-20 =1, that means the source of the Frequency command is from RS-485 Interface
(accessed by BACnet).
2-2. Set Pr.00-21 =2, that means the source of the Operation command is from RS-485 Interface
(accessed by BACnet).
Here is a simple example:
After setting up the 2 parts of Pr, we can enable the BACnet function in CFP2000. Thus, we can access
some BACnet objects to make the CFP2000 driving motor Run or Stop.
Step1. Write_Service on AV_001, Present_Value =60.0
Setup Frequency Reference Value.
Step2. Write_Service on BV_007, Present_Value =Active.
Setup Servo Power CMD.
Step3. Write_Service on BV_000, Present_Value =Active.
Setup Active CMD.
Step4. Read_Service on AV_031, Present_Value
User can know the Output frequency.
PS. In CFP2000, based on different Pr setting or IO setting, we can make FreqCmd with different source of Reference Value.
Please check the usage of Keypad, Pr and IO setting for more detail information.
Summary of Contents for CFP2000 Series
Page 3: ......
Page 12: ...Chapter 1 Introduction CFP2000 1 3 1 2 Model Name 1 3 Serial Number ...
Page 15: ...Chapter 1 Introduction CFP2000 1 6 Frame B RFI 1 RFI 1 RFI 1 RFI 2 RFI 2 RFI 2 Figure 1 5 ...
Page 37: ...Chapter 1 Introduction CFP2000 1 28 1 7 Digital Keypad KPC CC01 ...
Page 42: ...Chapter 3 Unpacking CFP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook ...
Page 54: ...Chapter 4 Wiring CFP2000 4 5 Figure 4 4 ...
Page 57: ...Chapter 4 Wiring CFP2000 4 8 4 4 Basic Waterproof Component Wiring Diagram Frame A Frame B ...
Page 58: ...Chapter 4 Wiring CFP2000 4 9 Frame C D0 ...
Page 75: ...Chapter 5 Main Circuit Terminals CFP2000 5 16 This page intentionally left blank ...
Page 120: ...Chapter 7 Optional Accessories CFP2000 7 35 Wall Mounting Embedded Mounting ...
Page 137: ...Chapter 7 Optional Accessories CFP2000 7 52 This page intentionally left blank ...
Page 173: ...Chapter 9 Specifications CFP2000 9 8 9 5 Efficiency Curve Figure 9 5 ...
Page 251: ...Chapter 11 Summary of Parameter Settings CFP2000 11 42 This page intentionally left blank ...
Page 304: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 3 3 4 5 ...
Page 305: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 4 6 7 8 ...
Page 306: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 5 9 10 11 ...
Page 307: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 6 12 13 14 ...
Page 308: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 7 15 16 17 ...
Page 309: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 8 18 19 20 ...
Page 310: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 9 21 22 23 ...
Page 311: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 10 24 25 26 ...
Page 312: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 11 27 28 29 ...
Page 313: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 12 30 31 32 ...
Page 314: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 13 33 34 35 ...
Page 315: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 14 36 37 38 ...
Page 326: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 25 ...
Page 545: ...Chapter 14 Fault Codes and Descriptions CFP2000 14 50 This page intentionally left blank ...
Page 726: ...Chapter 16 PLC Function Applications CFP2000 16 153 ...
Page 728: ...Chapter 16 PLC Function Applications CFP2000 16 155 ...
Page 731: ...Chapter 16 PLC Function Applications CFP2000 16 158 This page intentionally left blank ...
Page 747: ...Chapter 17 Introduction to BACnet CFP2000 17 16 This page intentionally left blank ...